Polarity (mutual inductance)

From Wikipedia, the free encyclopedia
  (Redirected from Dot convention)
Jump to: navigation, search
This article is about magnetically coupled transformer winding polarities. For motor winding polarity, see Electric motor.
HV side with dot conventions
LV side with dot conventions

The polarity of a device with mutual inductance designates the relative instantaneous current directions of such device's winding leads.[1]

A dot marking convention, or alphanumeric marking convention, or both, can be used to denote the same relative instantaneous polarity of two mutually inductive components such as between transformer windings. These markings may be found on transformer cases beside terminals, winding leads, nameplates, schematic and wiring diagrams.

Leads of primary and secondary windings are said be of the same polarity when instantaneous current entering the primary winding lead results in instantaneous current to leave the secondary winding lead as though the two leads were a continuous circuit.[1][2]

Transformer windings[edit]

Two methods are commonly used to denote which terminals present the same relative polarity. A dot may be used, or an alphanumeric designation. Alphanumeric designations are typically in the form H1 for primaries, and for secondaries, X1, (and Y1, Z1, if more windings present).

Unlike single-phase transformers, three-phase transformers may incorporate a phase shift due to different winding configurations resulting in a multiple of 30 degree phase shift between H1 and X1 bushing designations.

Terminal layout conventions[edit]

Referring to the circuit diagrams below:

The circuit polarity signs '+' and '-' indicate example applied and resultant, relative voltage polarities.
The instantaneous polarities of the voltages across each inductor with respect to the dotted terminals are the same.[3]
The circuit arrows indicate example applied and resultant relative current directions.
The instantaneous directions of the current entering the primary inductor at its dotted end and the current leaving of the secondary inductor at its dotted end are the same.
Subtractive polarity transformer designs are shown in the upper circuit diagrams. Additive polarity transformer designs are shown in the lower circuit diagrams.[4]

Mutual inductance.PNG

Autotransformers[edit]

If two mutually coupled inductors are in series, the dot convention can be used in the same manner as in the case of autotransformers. Relative polarity in autotransformer drawings is usually quite obvious by physical placement of the windings in circuit drawings.