Utilization categories

From Wikipedia, the free encyclopedia

This is an old revision of this page, as edited by 68.67.51.114 (talk) at 13:26, 7 July 2020 (Wrong term used on image). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

Usually utilization category is mentioned in most of the switch gear, with the above contactor stating to be used under AC1 - resistive load & AC3 for motor usage

In electrical engineering utilization categories are defined by IEC standards[1] and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.

Definition

The utilization categories category for low-voltage switchgear defines the characteristic operating conditions for switchgear such as contactors, circuit-breakers, circuit-breaker-fuse units, contactor relays, etc. These devices are dimensioned for different electrical loads and for different operating conditions.

The characteristic of the load to be switched or controlled determines the requirements for the switchgear and its correct selection for the intended application. In particular, the stress on the switching path caused by current and voltage during switching on and off is of enormous importance. For example, the switch-on and switch-off current at resistance load corresponds to the continuous operating current, while, for example, squirrel cage motors consumes multiple of the rated operating current during switch-on and in the acceleration phase.

Categorisation of Utilization category in IEC standard

Contact load in amperes for heaters (AC1) and motors (AC3) can be found directly on the contactor. The "Utilization category" are mainly categorized in IEC 60947 in the following volume:

  • Volume 1: General requirements
  • Volume 2: Circuit-breakers
  • Volume 3: Circuit-breakers, circuit-breakers, switch-disconnectors and switch-fuse units
  • Volume 4-1: Contactors and motor starters; electromechanical contactors and motor starters[1]
  • Volume 4-2: Contactors and motor starters - Semiconductor motor controllers and starters for a.c. voltage
  • Volume 5-1: Control apparatus and switching elements - Electromechanical control apparatus[1]
  • Volume 6-1: Multi-function switchgear and controlgear - Mains switches (categories AC-32A/B)
  • Volume 6-2: Multi-function switchgear and controlgear - Control and protective switchgear (CPS)
  • Volume 7-1: Auxiliary equipment; Terminal blocks for copper conductors
  • Volume 7-2: Ancillary equipment; protective conductor terminal blocks for copper conductors

In addition, IEC/EN 61095 also defines categories for "household and similar applications".

Table

The following table provides an overview of the various abbreviations. Within a utilization category, the suitable size may be selected for the respective type. This depends on the rated current, the rated voltage and the electrical load to be switched.

Utilization Category Typical Application[2][3] Applicable IEC norm[4]
AC-1 Non-inductive or slightly inductive loads, example: resistive furnaces, heaters 60947-4-1
AC-2 Slip-ring motors: switching off 60947-4-1
AC-3 Squirrel-cage motors: starting, switches off motors during running time 60947-4-1
AC-4 Squirrel-cage motors: starting, plugging, inching 60947-4-1
AC-5a Switching of discharge lamps 60947-4-1
AC-5b Switching of incandescent lamps 60947-4-1
AC-6a Switching of transformers 60947-4-1
AC-6b Switching of capacitor banks 60947-4-1
AC-7a Slightly inductive loads in household appliances: examples: mixers, blenders 60947-4-1
61095
AC-7b Motor-loads for household appliances: examples: fans, central vacuum 60947-4-1
61095
AC-8a Hermetic refrigerant compressor motor control with manual resetting overloads 60947-4-1
AC-8b Hermetic refrigerant compressor motor control with automatic resetting overloads 60947-4-1
AC-12 Control of resistive loads and solid state loads with opto-coupler isolation 60947-5-2
AC-13 Control of solid state loads with transformer isolation 60947-5-1
AC-14 Control of small electromagnetic loads 60947-5-1
AC-15 Control of A.C. electromagnetic loads 60947-5-1
AC-20 Connecting and disconnecting under no-load conditions 60947-3
AC-21 Switching of resistive loads, including moderate overloads 60947-3
AC-22 Switching of mixed resistive and inductive loads, including moderate overloads 60947-3
AC-23 Switching of motor loads or other highly inductive loads 60947-3
AC-31A
AC-31B ³)
Non-inductive or weakly inductive loads 60947-6-1
AC-33A
AC33B³)
Motor loads or mixed loads including motors, resistors and up to 30 % incandescent lamp load 60947-6-1
AC-35A
AC-35B ³)
Gas discharge lamp load 60947-6-1
AC-36A
AC36B ³)
Incandescent lamp load 60947-6-1
AC-40 Distribution circuits of mixed resistive and inductive loads 60947-6-2
AC-41 Non-inductive or weakly inductive loads, resistance furnaces 60947-6-2
AC-42 Slip ring motors: Starting, switching off 60947-6-2
AC-43 Squirrel cage motors: Starting, switching off during operation 60947-6-2
AC-44 Squirrel cage motors: Starting, counter-current braking ¹) or reversing ¹), typing ²) 60947-6-2
AC-45a Switching of gas discharge lamps 60947-6-2
AC-45b Switching incandescent lamps 60947-6-2
AC-51 Induction-free or slightly inductive loads, resistance furnaces 60947-4-3
AC-52a Control of the stator winding of a slip-ring motor: 8-hour operation with starting currents for starting processes, maneuvering, operation 60947-4-2
AC-52b Control of the stator winding of a slip ring motor: Intermittent operation 60947-4-2
AC-53a Control of a squirrel cage motor: 8-hour operation with starting currents for starting processes, maneuvering, operation 60947-4-2
AC-53b Control of a squirrel cage motor: Intermittent operation 60947-4-2
AC-55a Switching of electrical controls of discharge lamps 60947-4-3
AC-55b Switching incandescent lamps 60947-4-3
AC-56a Switching transformers 60947-4-3
AC-56b Switching of capacitor batteries 60947-4-3
AC-58a Control of a hermetically sealed refrigeration compressor motor with automatic reset of overload releases: 8-hour operation with starting currents for starting, maneuvering, operation 60947-4-2
AC-58b The control of a hermetically sealed refrigeration compressor motor with automatic reset of the overload trips: Intermittent operation 60947-4-2
AC-140 Control of small electromagnetic loads with holding current ≤ 0.2 A; e.g. contactor relays 60947-5-2
A Protection of circuits, with no rated short-time withstand current 60947-3
B Protection of circuits, with a rated short-time withstand current 60947-3
DC-1 Non Inductive or slightly inductive loads, resistance furnaces, heaters 60947-4-1
DC-3 Shunt-motors, starting, plugging(1), inching(2), dynamic braking of motors 60947-4-1
DC-5 Series-motors, starting, plugging(1), inching(2), dynamic braking of motors 60947-4-1
DC-6 Switching of incandescent lamps 60947-4-1
DC-12 Control of resistive loads and solid state loads with opto-coupler isolation 60947-5-1
60947-5-2
DC-13 Control of D.C. electromagnetics 60947-5-1
60947-5-2
DC-14 Control of D.C. electromagnetic loads having economy resistors in the circuit 60947-5-1
DC-20 Connecting and disconnecting under no-load conditions 60947-5-1
DC-21 Switching of resistive loads, including moderate overloads 60947-5-1
DC-22 Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors) 60947-5-1
DC-23 Switching of highly inductive loads (i.e. series motors) 60947-5-1

See also

References