Tir John power station
Map
CountryWales
LocationSwansea
Coordinates51°37′35″N 03°53′50″W / 51.62639°N 3.89722°W / 51.62639; -3.89722
StatusDecommissioned and demolished
Construction began1932
Commission date1935
Decommission date1976
OwnersSwansea Corporation
(1932–1948)
British Electricity Authority
(1948–1955)
Central Electricity Authority
(1955–1957)
Central Electricity Generating Board
(1958–1976)
OperatorAs owner
Thermal power station
Primary fuelCoal, later oil
Turbine technologySteam turbines
Chimneys2
Cooling sourceSeawater
Power generation
Units operational2 x 30 MW, 2 x 41.5 MW, 1 x 12.5 MW
Make and modelBrush-Ljungstrom, Parsons, British Thomson-Houston
Nameplate capacity142 MW
Annual net output784 GWh (1956)

Tir John power station supplied electricity to the Swansea area and to the national grid from 1935 to 1976. It was initially owned and operated by the Swansea Corporation until the nationalisation of the electricity supply industry in 1948. The power station was built in several phases from 1935 to 1944. It was converted from coal to oil-firing in 1967; Tir John power station was decommissioned in 1976.

History

Swansea Corporation planned to build Tir John power station partly as an unemployment relief scheme, in the early 1930s.[1] It was designed to be an integral part of the recently commissioned national grid (built 1927-33).[2] The plans for Tir John were sanctioned in 1931 and construction started the following year.[3] At that time it was the largest construction project in Wales.[1] The power station was officially opened on 20 June 1935.[3] [4]

Equipment specification

The first equipment to be commissioned was the low pressure (LP) plant comprising a British Thomson-Houston 12.5 MW turbo-alternator.[3] This was supplied with stream at 250 psi and 795 °F (17.2 bar at 424°C). Current was generated at 6.6 kV.

Further plant was commissioned in 1935, 1941 and 1944. When completed the station comprised:[3]

  • Boilers
    • 4 × International Combustion tri-drum boilers evaporating at 230,000 lb/h (29.00 kg/s) and operating at 625 psi and 850 °F (43.1 bar and 454 °C).
    • 4 × International Combustion tri-drum boilers evaporating at 240,000 lb/h (30.2 kg/s) and also operating at 625 psi and 850 °F.

The boilers were supplied with pulverised coal produced from waste anthracite duff by Hardinge ball mills.[3]

The boilers could deliver a total of 1,880,000 lb/h (23.7 kg/s) of steam to:

  • Turbo-alternators
    • 2 × Parsons 30 MW turbo-alternators with a maximum continuous capacity of 33 kV, 0.8 P.F., 50 Hz, 3,000 rpm, generating at 33 kV. Operated by steam at 600 psi and 825°F (41.4 bar and 441 °C).
    • 2 × Brush-Ljungstrom 41.5 MW turbo-alternators, one generating at 33 kV and one at 132 kV, 0.75 P.F., 50 Hz, 1,500 rpm. Operated by steam at 600 psi and 825°F (41.4 bar and 441 °C).

Cooling water for the condensers was taken from Kings Dock via a 900 yard (823 m) long, 9 foot diameter (2.44 m) tunnel. Water was discharged into Queens Dock via a 1,300 yard (1189) long tunnel of the same diameter.[3][5]

The power station included a flue-gas washing plant to remove sulphur oxides and dust from the gases. There were four scrubbers, one for each boiler, constructed of steel plates, each contained wooden grids sprayed with water treated with lime. Flue-gases passed vertically through the grids, the water /lime solution dissolving the sulphur compounds. Water from the base of the scrubbers passed to holding tanks to allow the chemical reactions to complete. The water was recirculated to the scrubbers, with some drawn off to remove the solids. Make-up water for the scrubbers was drawn from Crymlyn Bog.[6]

Operations

Tir John power station was operated by Swansea Corporation under the direction of the Central Electricity Board from 1935 and though the Second World War until 1948.[7]

Tir John power station operating on anthracite duff had the cheapest fuel costs of any power station in the country.[2]

The connection to the national grid was at a 132 kV substation south of the power station.[8]

The British electricity supply industry was nationalised in 1948 under the provisions of the Electricity Act 1947 (10-11 Geo. 6 c. 54).[9] The Swansea Corporation electricity undertaking was abolished, ownership of Tir John power station was vested in the British Electricity Authority, and subsequently the Central Electricity Authority and the Central Electricity Generating Board (CEGB).[10] At the same time the electricity distribution and sales responsibilities of the Swansea electricity undertaking were transferred to the South Wales Electricity Board (SWALEB).

The CEGB converted the boilers to run on oil in 1967. This was to take advantage of fuel supplies from the nearby Llandarcy oil refinery.[1]

Operational data

Operating data for the period 1946–72 is given in the table:[11][3][12][13]

Tir John power station operating data, 1946–72.
Year Running hours or load factor (per cent) Max output capacity  MW Electricity supplied GWh Thermal efficiency per cent
1946 56.8 % 99.60 495.45 20.44
1954 8760 142 771.37 19.49
1955 8760 142 776.30 19.01
1956 8784 142 783.69 19.41
1957 8760 142 696.88 19.31
1958 8760 142 660.41 18.16
1961 40.1 % 142 498.67 15.83
1962 16.9 % 142 209.76 15.01
1963 17.93 % 142 223.00 13.69
1967 10.5 142 130.62 14.36
1972 31.6 % 64 205.26 19.43

The less intensive use of the station after 1956 is evident.

Electricity supplied (GWh)

Closure

Tir John power station was decommissioned in 1976.[1]  The buildings subsequently demolished. The 132 kV substation and its connections to the national grid is extant (2020).[14]

See also

References

  1. ^ a b c d "Tir John power station". coflein. 25 October 2013. Retrieved 14 August 2020.{{cite web}}: CS1 maint: url-status (link)
  2. ^ a b Hannah, Leslie (1979). Electricity before Nationalisation. London: Macmillan. pp. 132, 135. ISBN 0333220862.
  3. ^ a b c d e f g Garrett, Frederick C. ed. (1959). Garcke's Manual of Electricity Supply vol.56. London: Electrical Press. pp. A-101, A-136. {{cite book}}: |first= has generic name (help)
  4. ^ "Tir John power station". Britain from above. 1939. Retrieved 14 August 2020.{{cite web}}: CS1 maint: url-status (link)
  5. ^ "Swansea Docks Tir John power station". Swansea docks. Retrieved 15 August 2020.{{cite web}}: CS1 maint: url-status (link)
  6. ^ Institution of Mechanical Engineers, Visits to Works 1938. Swansea Corporation Electricity Undertaking Tir John Power Station
  7. ^ "Wonders of World Engineering". 5 October 1937.{{cite web}}: CS1 maint: url-status (link)
  8. ^ "Ordnance Survey 6-inch Glamorgan XXIV.NW". Old maps online. 1951. Retrieved 14 August 2020.{{cite web}}: CS1 maint: url-status (link)
  9. ^ "Electricity Act 1947". legislation.gov.uk. 1947. Retrieved 14 August 2020.{{cite web}}: CS1 maint: url-status (link)
  10. ^ Electricity Council (1987). Electricity Supply in the United Kingdom: a Chronology. London: Electricity Council. pp. 45, 60, 69, 73. ISBN 085188105X.
  11. ^ Electricity Commission. Generation of Electricity in Great Britain year ended 31 December 1946. London: HMSO. p. 14.
  12. ^ CEGB Annual Reports 1961, 1962 1963 London CEGB
  13. ^ CEGB (1972). CEGB statistical Yearbook 1972. London: CEGB. p. 11.
  14. ^ "Open Infrastructure Map". Open Infrastructure Map. Retrieved 14 August 2020.{{cite web}}: CS1 maint: url-status (link)