Line 57: Line 57:
In general, FACTs devices improve power and voltage in three different ways: Shunt Compensation of Voltage (replacing the function of [[Capacitor|capacitors]] or [[Inductor|inductors]]), Series Compensation of Impedance (replacing [[Series capacitor|series capacitors]]) or Phase-Angle Compensation (replacing [[Voltage droop|Generator Droop-Control]] or [[Quadrature booster|Phase-Shifting Transformers]]). While other traditional equipment can accomplish all of this, FACTs devices utilize Power Electronics that are fast enough to switch [[Frequency|sub-cycle]] opposed to seconds or minutes. Most FACTs devices are also dynamic and can support voltage across a range rather than just on and off, and are multi-quadrant, i.e. they can both supply and consume [[Reactive power|Reactive Power]], and even sometimes [[Real power|Real Power]]. All of this give them their "flexible" nature and make them well-suited for applications with unknown or changing requirements.
In general, FACTs devices improve power and voltage in three different ways: Shunt Compensation of Voltage (replacing the function of [[Capacitor|capacitors]] or [[Inductor|inductors]]), Series Compensation of Impedance (replacing [[Series capacitor|series capacitors]]) or Phase-Angle Compensation (replacing [[Voltage droop|Generator Droop-Control]] or [[Quadrature booster|Phase-Shifting Transformers]]). While other traditional equipment can accomplish all of this, FACTs devices utilize Power Electronics that are fast enough to switch [[Frequency|sub-cycle]] opposed to seconds or minutes. Most FACTs devices are also dynamic and can support voltage across a range rather than just on and off, and are multi-quadrant, i.e. they can both supply and consume [[Reactive power|Reactive Power]], and even sometimes [[Real power|Real Power]]. All of this give them their "flexible" nature and make them well-suited for applications with unknown or changing requirements.


The FACTs family initially grew out of the development of [[High-voltage direct current|High-Voltage Direct-Current (HVDC)]] conversion and transmission, which used Power Electronics to convert AC to [[Direct current|DC]] to enable large, controllable power transfers. While HVDC focused on conversion to DC, FACTs devices used the developed technology to control power and voltage on the AC system. The most common type of FACTs device is the [[Static VAR compensator|Static VAR Compensator (SVC)]], which uses [[Thyristor|Thyristors]] to switch and control shunt capacitors and reactors, respectively.
The FACTs family initially grew out of the development of [[High-voltage direct current|High-Voltage Direct-Current (HVDC)]] conversion and transmission, which used Power Electronics to convert AC to [[Direct current|DC]] to enable large, controllable power transfers<ref>EPRI High Voltage Direct Current (HVDC) Transmission Reference Book EPRI, Palo Alto, CA: 2017. 1020401.</ref>. While HVDC focused on conversion to DC, FACTs devices used the developed technology to control power and voltage on the AC system. The most common type of FACTs device is the [[Static VAR compensator|Static VAR Compensator (SVC)]], which uses [[Thyristor|Thyristors]] to switch and control shunt capacitors and reactors, respectively.


== History ==
== History ==
Line 72: Line 72:
==Theory==
==Theory==
The basic theory for how FACTs devices affect the AC system is based on analyzing how power transfers between two points in an AC system. This is particularly relevant to how an AC electrical grid functions, as the grid has numerous nodes (substations) that lack sources ([[Alternator|generators]]) or [[Electrical load|loads]]. Power flow must be calculated and controlled at each node (substation bus) to ensure the grid design and topology itself does not prevent generated [[electricity]] from reaching loads<ref>{{Cite book |last1=Kumar |first1=Yogesh |last2=Devabhaktuni |first2=Vijay K. |last3=Vemuru |first3=Srinivasa |chapter=Comparison of power system simulation tools with load flow study cases |date=May 2015 |title=2015 IEEE International Conference on Electro/Information Technology (EIT) |chapter-url=https://ieeexplore.ieee.org/document/7293355 |publisher=IEEE |pages=290–294 |doi=10.1109/EIT.2015.7293355 |isbn=978-1-4799-8802-0}}</ref>, as when Transmission Lines reach dozens to hundreds of miles in length, they add significant impedance and voltage drop to the system.
The basic theory for how FACTs devices affect the AC system is based on analyzing how power transfers between two points in an AC system. This is particularly relevant to how an AC electrical grid functions, as the grid has numerous nodes (substations) that lack sources ([[Alternator|generators]]) or [[Electrical load|loads]]. Power flow must be calculated and controlled at each node (substation bus) to ensure the grid design and topology itself does not prevent generated [[electricity]] from reaching loads<ref>{{Cite book |last1=Kumar |first1=Yogesh |last2=Devabhaktuni |first2=Vijay K. |last3=Vemuru |first3=Srinivasa |chapter=Comparison of power system simulation tools with load flow study cases |date=May 2015 |title=2015 IEEE International Conference on Electro/Information Technology (EIT) |chapter-url=https://ieeexplore.ieee.org/document/7293355 |publisher=IEEE |pages=290–294 |doi=10.1109/EIT.2015.7293355 |isbn=978-1-4799-8802-0}}</ref>, as when Transmission Lines reach dozens to hundreds of miles in length, they add significant impedance and voltage drop to the system.
Given two buses, each with their own voltage [[Vector space|magnitude and phase angle]], and connected by a Transmission Line with an impedance, the current flowing between them is given by[[File:FACTS theory1.PNG|thumb|335x335px|A simple Circuit Diagram showing two buses connected through an impedance, with a Vector Diagram representing the phase-angle between them]]<math>\bar{I}=\frac{\bar{V}_s-\bar{V}_r}{\bar{Z}_L}</math>
Given two buses, each with their own voltage [[Vector space|magnitude and phase angle]], and connected by a Transmission Line with an impedance, the current flowing between them is given by<ref>{{Cite book |last=Mohan |first=Ned |title=First course on power systems |date=2007 |publisher=MNPERE |isbn=978-0-9715292-7-4 |edition=Year 2006 Edition; revised July 2007 |location=Minneapolis}}</ref>[[File:FACTS theory1.PNG|thumb|335x335px|A simple Circuit Diagram showing two buses connected through an impedance, with a Vector Diagram representing the phase-angle between them]]<math>\bar{I}=\frac{\bar{V}_s-\bar{V}_r}{\bar{Z}_L}</math>


Apparent Power flow, and thus real and reactive power, is then given by
Apparent Power flow, and thus real and reactive power, is then given by
Line 94: Line 94:
<math>\delta</math> is the phase angle difference between the sending-end and receiving end voltages
<math>\delta</math> is the phase angle difference between the sending-end and receiving end voltages


From the above equations, it can be seen that there are three variables that affect real and reactive power flow on a Transmission Line: the voltage magnitudes at either bus, the line reactance between the buses, and the voltage phase-angle difference between the buses. All FACTs devices operation on the fundamental principal that changing one or more of these variables will change the real and reactive power flow on the transmission line<ref>{{Cite book |last1=Okeke |first1=Therese Uzochukwuamaka |last2=Zaher |first2=Ramy Georgious |chapter=Flexible AC Transmission Systems (FACTS) |date=December 2013 |pages=1–4 |title=2013 International Conference on New Concepts in Smart Cities: Fostering Public and Private Alliances (SmartMILE) |chapter-url=http://dx.doi.org/10.1109/smartmile.2013.6708208 |publisher=IEEE |doi=10.1109/smartmile.2013.6708208|hdl=10651/37597 |isbn=978-1-4799-2911-5 }}</ref>. Some FACTs devices will just change a single variable, while others will control all three.
From the above equations, it can be seen that there are three variables that affect real and reactive power flow on a Transmission Line<ref>{{Cite book |last=Hingorani |first=Narain G. |title=Understanding FACTS: concepts and technology of flexible AC transmission systems |last2=Gyugyi |first2=Laszlo |date=2000 |publisher=IEEE Press |isbn=978-0-7803-3455-7 |location=New York}}</ref>: the voltage magnitudes at either bus, the line reactance between the buses, and the voltage phase-angle difference between the buses. All FACTs devices operation on the fundamental principal that changing one or more of these variables will change the real and reactive power flow on the transmission line. Some FACTs devices will just change a single variable, while others will control all three.


It should be noted, and will be made more explicit below, that FACTs devices do not create or add real power to the system, they simply affect the circuit parameters between two points to affect how and when power flows.
It should be noted, and will be made more explicit below, that FACTs devices do not create or add real power to the system, they simply affect the circuit parameters between two points to affect how and when power flows.
Line 102: Line 102:


=== Shunt Compensation Devices ===
=== Shunt Compensation Devices ===
The goal shunt compensation is to connect a device in parallel with the system that will improve voltage and enable larger power flow. This is traditionally done using shunt capacitors and inductors (reactors), much like [[Power factor|Power Factor Correction]].
The goal shunt compensation is to connect a device in parallel with the system that will improve voltage and enable larger power flow. This is traditionally done using shunt capacitors and inductors (reactors)<ref>EPRI Increased Power Flow Guidebook—2017: Increasing Power Flow in Lines, Cables, and Substations. EPRI, Palo Alto, CA: 2017. 3002010150.</ref>, much like [[Power factor|Power Factor Correction]].


The most common shunt compensation device is the [[Static VAR compensator|Static VAR Compensator (SVC)]]. SVCs use power electronics, generally [[Thyristor|Thyristors]], to switch fixed capacitors and reactors. These are referred to as [[Static VAR compensator|Thyristor Switched Capacitor (TSC)]] and [[Static VAR compensator|Thyristor Switched Reactor (TSR)]], respectively. Thyristors are fast enough that they can be switched sub-cycle, and can switch a reactor at different points each cycle to control the [[Volt-ampere|vars]] the reactor produces. When arranged to do this, the TSR is referred to as a [[Static VAR compensator|Thyristor Controlled Reactor (TCR)]]. TCRs produce large amounts of [[Harmonic|harmonics]] and require [[Low-pass filter|Filter Banks]] to prevent adverse effects to the system.
The most common shunt compensation device is the [[Static VAR compensator|Static VAR Compensator (SVC)]].<ref>EPRI Power Electronics-Based Transmission Controllers Reference Book ("The Gold Book") EPRI, Palo Alto, CA: 2017. 1020401.</ref> SVCs use power electronics, generally [[Thyristor|Thyristors]], to switch fixed capacitors and reactors. These are referred to as [[Static VAR compensator|Thyristor Switched Capacitor (TSC)]] and [[Static VAR compensator|Thyristor Switched Reactor (TSR)]], respectively. Thyristors are fast enough that they can be switched sub-cycle, and can switch a reactor at different points each cycle to control the [[Volt-ampere|vars]] the reactor produces. When arranged to do this, the TSR is referred to as a [[Static VAR compensator|Thyristor Controlled Reactor (TCR)]]. TCRs produce large amounts of [[Harmonic|harmonics]] and require [[Low-pass filter|Filter Banks]] to prevent adverse effects to the system.


Another type of shunt compensation is the [[Static synchronous compensator|Static Synchronous Compensator or STATCOM]]. Power electronics are combined in series with a reactor to form a Voltage-Sourced Converter (VSC), which when connected to an AC system forms a STATCOM. A VSC use the same principal of power flow on a transmission line; measuring the system voltage its connected to and varying the voltage of the power electronics to cause reactive power flow in or out of the VSC. Early STATCOMs used thyristors as their power electronics and [[Pulse-width modulation|Pulse-Width Modulation (PWM)]] to control reactive power, but with advances in semiconductor technologies, [[Insulated-gate bipolar transistor|Insulated-Gate Bipolar Transistors (IGBT)]] have replaced them.
Another type of shunt compensation is the [[Static synchronous compensator|Static Synchronous Compensator or STATCOM]]. Power electronics are combined in series with a reactor to form a Voltage-Sourced Converter (VSC), which when connected to an AC system forms a STATCOM<ref>{{Cite book |last=Sood |first=Vijay K. |title=HVDC and FACTS controllers: applications of static converters in power systems |date=2004 |publisher=Kluwer Academic Publishers |isbn=978-1-4020-7890-3 |series=Power electronics and power systems |location=Boston}}</ref>. A VSC use the same principal of power flow on a transmission line; measuring the system voltage its connected to and varying the voltage of the power electronics to cause reactive power flow in or out of the VSC. Early STATCOMs used thyristors as their power electronics and [[Pulse-width modulation|Pulse-Width Modulation (PWM)]] to control reactive power, but with advances in semiconductor technologies, [[Insulated-gate bipolar transistor|Insulated-Gate Bipolar Transistors (IGBT)]] have replaced them.


=== Series Compensation Devices ===
=== Series Compensation Devices ===
Series Compensation devices change the impedance of the Transmission Line to increase or decrease power flow. Power flow is increased by adding a [[Series and parallel circuits|series capacitor]] to offset line inductance, or decreased by adding a series load-flow reactor to add to the line inductance.
Series Compensation devices change the impedance of the Transmission Line to increase or decrease power flow. Power flow is increased by adding a [[Series and parallel circuits|series capacitor]] to offset line inductance or decreased by adding a series load-flow reactor to add to the line inductance.


One type of series compensation is the [[Thyristor-Controlled Series Capacitor|Thyristor-Controlled Series Capacitor (TCSC)]], which combines the TCR from an SVC in parallel with a traditional fixed series capacitor. As using power electronics to switch capacitors sub-cycle is not feasible due to concerns of stored charge, a TCR is used to create a variable inductance to offset the capacitor. A TCSC can be used to dynamically vary the power flow on a transmission line.
One type of series compensation is the [[Thyristor-Controlled Series Capacitor|Thyristor-Controlled Series Capacitor (TCSC)]], which combines the TCR from an SVC in parallel with a traditional fixed series capacitor. As using power electronics to switch capacitors sub-cycle is not feasible due to concerns of stored charge, a TCR is used to create a variable inductance to offset the capacitor. A TCSC can be used to dynamically vary the power flow on a transmission line.<ref>{{Cite journal |last=Cao |first=Foqing |last2=Hu |first2=Lei |last3=Zhang |first3=Jingtao |last4=Almenweer |first4=Reem A. |last5=Alnasseir |first5=Jamal |last6=Almaghout |first6=Fadi |date=2023-12-15 |title=Study on Power Flow Improvement Using Static Compensators and Thyristor Controlled Series Capacitor in Transmission Network |url=https://ieeexplore.ieee.org/document/10420634/ |publisher=IEEE |pages=354–359 |doi=10.1109/CEECT59667.2023.10420634 |isbn=979-8-3503-4225-3}}</ref>


A VSC can also be used as a series compensation device if its connected across the secondary winding of a series-connected transformer. This arrangement is referred to as a [[Static synchronous series compensator|Static Synchronous Series Compensator (SSSC)]], and offers the benefits of a smaller reactor than in a TCSC, and the lower harmonic production of a VSC (or Voltage-Source Inverter - VSI when used in a SSSC) compared to a TCR.
A VSC can also be used as a series compensation device if it's connected across the secondary winding of a series-connected transformer. This arrangement is referred to as a [[Static synchronous series compensator|Static Synchronous Series Compensator (SSSC)]]<ref>{{Cite book |last=Hingorani |first=Narain G. |title=Understanding FACTS: concepts and technology of flexible AC transmission systems |last2=Gyugyi |first2=Laszlo |date=2000 |publisher=IEEE Press |isbn=978-0-7803-3455-7 |location=New York}}</ref>, and offers the benefits of a smaller reactor than in a TCSC, and the lower harmonic production of a VSC (or Voltage-Source Inverter - VSI when used in a SSSC) compared to a TCR.


=== Phase Angle Compensation ===
=== Phase Angle Compensation ===
Power will only flow between two points on an AC system if there is a phase angle difference between the buses. Traditionally this is controlled by generators, however in large grids this becomes ineffective for managing power flow between distant buses. Phase-Shifting Transformers (PST) are generally used for these applications and can just be a [[Phase-Angle Regulator (PAR)]] or [[Quadrature booster|control both phase-angle and voltage]].
Power will only flow between two points on an AC system if there is a phase angle difference between the buses. Traditionally this is controlled by generators, however in large grids this becomes ineffective for managing power flow between distant buses. Phase-Shifting Transformers (PST) are generally used for these applications and can just be a [[Phase-Angle Regulator (PAR)]] or [[Quadrature booster|control both phase-angle and voltage]].


The most straightforward phase angle compensation device would be to replace the tap changer on PAR with thyristors to switch portions of the winding in and out, forming a [[Thyristor-Controlled Phase-Angle Regulator (TCPAR)]]. However, this is generally not done as a TCPAR would be considerably more expensive than a PAR. Instead, the idea of a TCPAR is expanded to replace a Quadrature Booster PST with a device referred to as a [[Static Phase Shifter (SPS)]]. From the schematic, it can be seen that a SPS is similar to a combining a TCVR and TCPAR, by replacing the mechanical portions of the excitor and booster transformers. respectively.
The most straightforward phase angle compensation device would be to replace the tap changer on PAR with thyristors to switch portions of the winding in and out, forming a [[Thyristor-Controlled Phase-Angle Regulator (TCPAR)]].<ref>{{Cite journal |last=Rezvanfar |first=R. |last2=Mosayebian |first2=M. E. |last3=Monsef |first3=H. |last4=Ghasemi |first4=H. |date=2011-05 |title=Impact of optimally located thyristor controlled phase angle regulator on system security and reliability |url=http://dx.doi.org/10.1109/eeeic.2011.5874829 |journal=2011 10th International Conference on Environment and Electrical Engineering |publisher=IEEE |doi=10.1109/eeeic.2011.5874829}}</ref> However, this is generally not done as a TCPAR would be considerably more expensive than a PAR. Instead, the idea of a TCPAR is expanded to replace a Quadrature Booster PST with a device referred to as a [[Static Phase Shifter (SPS)]].<ref>{{Cite book |title=Flexible ac transmission systems (FACTS) |date=1999 |publisher=Institution of Electrical Engineers |isbn=978-0-85296-771-3 |editor-last=Song |editor-first=Yong-hua |series=IEE power and energy series |location=London |editor-last2=Johns |editor-first2=Allan T.}}</ref> From the schematic, it can be seen that a SPS is similar to a combining a TCVR and TCPAR, by replacing the mechanical portions of the excitor and booster transformers. respectively.


Another way to control a transformer with thyristor is through a [[Thyristor Controlled Voltage Regulator (TCVR)]], which uses pairs of thyristors to switch parts of the secondary transformer's winding sub-cycle, effectively changing the secondary voltage produced dynamically. This arrangement forms a device very similar to Tap-Changer, and functions much like a TCR. Technically, while a TCVR just controls voltage and not phase angle, it could be used to replace the taps or a PAR, and a version of it is used is a SPS. It is also often lumped with phase angle compensation devices due to its similar topology.
Another way to control a transformer with thyristor is through a [[Thyristor Controlled Voltage Regulator (TCVR)]]<ref>{{Cite journal |last=Asabin |first=Anatolij |last2=Sosnina |first2=Elena |last3=Belyanin |first3=Igor |last4=Bedretdinov |first4=Rustam |last5=Kryukov |first5=Evgeny |date=2020-06-29 |title=Control System of the Thyristor Voltage Regulator |url=https://ieeexplore.ieee.org/document/9263984/ |publisher=IEEE |pages=802–806 |doi=10.1109/CoDIT49905.2020.9263984 |isbn=978-1-7281-5953-9}}</ref>, which uses pairs of thyristors to switch parts of the secondary transformer's winding sub-cycle, effectively changing the secondary voltage produced dynamically. This arrangement forms a device very similar to Tap-Changer, and functions much like a TCR. Technically, while a TCVR just controls voltage and not phase angle, it could be used to replace the taps or a PAR, and a version of it is used is a SPS. It is also often lumped with phase angle compensation devices due to its similar topology.


==See also==
==See also==

Revision as of 17:36, 8 April 2024

A Flexible Alternating Current Transmission System (FACTS) is a family of Power-Electronic based devices designed for use on an Alternating Current (AC) Transmission System to improve and control Power Flow and support Voltage. FACTs devices are alternatives to traditional electric grid solutions and improvements, where building additional Transmission Lines or Substation is not economically or logistically viable.

In general, FACTs devices improve power and voltage in three different ways: Shunt Compensation of Voltage (replacing the function of capacitors or inductors), Series Compensation of Impedance (replacing series capacitors) or Phase-Angle Compensation (replacing Generator Droop-Control or Phase-Shifting Transformers). While other traditional equipment can accomplish all of this, FACTs devices utilize Power Electronics that are fast enough to switch sub-cycle opposed to seconds or minutes. Most FACTs devices are also dynamic and can support voltage across a range rather than just on and off, and are multi-quadrant, i.e. they can both supply and consume Reactive Power, and even sometimes Real Power. All of this give them their "flexible" nature and make them well-suited for applications with unknown or changing requirements.

The FACTs family initially grew out of the development of High-Voltage Direct-Current (HVDC) conversion and transmission, which used Power Electronics to convert AC to DC to enable large, controllable power transfers[1]. While HVDC focused on conversion to DC, FACTs devices used the developed technology to control power and voltage on the AC system. The most common type of FACTs device is the Static VAR Compensator (SVC), which uses Thyristors to switch and control shunt capacitors and reactors, respectively.

History

When AC won the War of Currents in the late 19th century, and electric grids began expanding and connecting cities and states, the need for reactive compensation became apparent.[2] While AC offered benefits with transformation and reduced current, the alternating nature of voltage and current lead to additional challenges with the natural capacitance and inductance of transmission lines. Heavily loaded lines consumed reactive power due to the line's inductance, and as transmission voltage increased throughout the 20th century, the higher voltage supplied capacitive reactive power. As operating a transmission line only at it surge impedance loading (SIL) was not feasible,[2] other means to manage the reactive power was needed.

A mercury-arc Valve used for high-voltage power electronics.

Synchronous Machines were commonly used at the time for generators, and could provide some reactive power support, however were limited due to the increase in losses it caused. They also became less effective as higher voltage transmissions lines moved loads further from sources. Fixed, shunt capacitor and reactor banks filled this need by being deployed where needed. In particular, shunt capacitors switched by circuit breakers provided an effective means to managing varying reactive power requirements due to changing loads.[3] However, this was not without limitations.

Shunt capacitors and reactors are fixed devices, only able to be switched on and off. This required either a careful study of the exact size needed,[4] or accepting less than ideal effects on the voltage of a transmission line. The need for a more dynamic and flexible solution was realized with the mercury-arc valve in the early 20th century. Similar to a vacuum tube, the mercury-arc valve was a high-powered rectifier, capable of converting high AC voltages to DC. As the technology improved, inverting became possible as well and mercury valves found use in power systems and HVDC ties. When connected to a reactor, different switching pattern could be used to vary the effective inductance connected,[5] allow for more dynamic control. Arc valves continued to dominate power electronics until the rise of solid-state semiconductors in the mid 20th century.[6]

As semiconductors replaced vacuum tubes, the thyristor created the first modern FACTs devices in the Static VAR Compensator (SVC).[7] Effectively working as a circuit breaker that could switch on in milliseconds, it allowed for quickly switching capacitor banks. Connected to a reactor and switched sub-cycle allowed the effective inductance to be varied. The thyristor also greatly improved the control system, allowing an SVC to detect and react to faults to better support the system.[8] The thyristor dominated the FACTs and HVDC world until the late 20th century, when the IGBT began to match its power ratings.[9]

Theory

The basic theory for how FACTs devices affect the AC system is based on analyzing how power transfers between two points in an AC system. This is particularly relevant to how an AC electrical grid functions, as the grid has numerous nodes (substations) that lack sources (generators) or loads. Power flow must be calculated and controlled at each node (substation bus) to ensure the grid design and topology itself does not prevent generated electricity from reaching loads[10], as when Transmission Lines reach dozens to hundreds of miles in length, they add significant impedance and voltage drop to the system.

Given two buses, each with their own voltage magnitude and phase angle, and connected by a Transmission Line with an impedance, the current flowing between them is given by[11]

A simple Circuit Diagram showing two buses connected through an impedance, with a Vector Diagram representing the phase-angle between them

Apparent Power flow, and thus real and reactive power, is then given by

Combining these two equations gives the real and reactive power flow as a function of voltages and impedance. This can be done relatively easily, and is done in load-flow and power analysis programs, but results in equations that are not intuitive to understand. Two approximations can be made to simplify things: assume a lossless Transmission Line (a decent assumption as very low resistance conductor is typically used) and neglecting any capacitance on the line (a fair assumption for 200kV lines and lower). This reduces the Line impedance to just a reactance, and results in the real and reactive power being

where

is the magnitude of the Sending-End Voltage, at the first bus

is the magnitude of the Receiving-End Voltage, at the second bus

is the reactance of the Transmission Line between the buses

is the phase angle difference between the sending-end and receiving end voltages

From the above equations, it can be seen that there are three variables that affect real and reactive power flow on a Transmission Line[12]: the voltage magnitudes at either bus, the line reactance between the buses, and the voltage phase-angle difference between the buses. All FACTs devices operation on the fundamental principal that changing one or more of these variables will change the real and reactive power flow on the transmission line. Some FACTs devices will just change a single variable, while others will control all three.

It should be noted, and will be made more explicit below, that FACTs devices do not create or add real power to the system, they simply affect the circuit parameters between two points to affect how and when power flows.

Types of FACTs devices

Given that FACTs device can change up to three parameters to affect power flow (voltage, impedance, and/or phase-angle), they are often categorized by what parameter they are controlling. As the conventional devices for controlling voltage (shunt capacitors and shunt inductors) and impedance (series capacitors and load-flow reactors) are so common, FACTs devices targeting voltage and impedance parameters are categorized as shunt and series devices, respectively.

Shunt Compensation Devices

The goal shunt compensation is to connect a device in parallel with the system that will improve voltage and enable larger power flow. This is traditionally done using shunt capacitors and inductors (reactors)[13], much like Power Factor Correction.

The most common shunt compensation device is the Static VAR Compensator (SVC).[14] SVCs use power electronics, generally Thyristors, to switch fixed capacitors and reactors. These are referred to as Thyristor Switched Capacitor (TSC) and Thyristor Switched Reactor (TSR), respectively. Thyristors are fast enough that they can be switched sub-cycle, and can switch a reactor at different points each cycle to control the vars the reactor produces. When arranged to do this, the TSR is referred to as a Thyristor Controlled Reactor (TCR). TCRs produce large amounts of harmonics and require Filter Banks to prevent adverse effects to the system.

Another type of shunt compensation is the Static Synchronous Compensator or STATCOM. Power electronics are combined in series with a reactor to form a Voltage-Sourced Converter (VSC), which when connected to an AC system forms a STATCOM[15]. A VSC use the same principal of power flow on a transmission line; measuring the system voltage its connected to and varying the voltage of the power electronics to cause reactive power flow in or out of the VSC. Early STATCOMs used thyristors as their power electronics and Pulse-Width Modulation (PWM) to control reactive power, but with advances in semiconductor technologies, Insulated-Gate Bipolar Transistors (IGBT) have replaced them.

Series Compensation Devices

Series Compensation devices change the impedance of the Transmission Line to increase or decrease power flow. Power flow is increased by adding a series capacitor to offset line inductance or decreased by adding a series load-flow reactor to add to the line inductance.

One type of series compensation is the Thyristor-Controlled Series Capacitor (TCSC), which combines the TCR from an SVC in parallel with a traditional fixed series capacitor. As using power electronics to switch capacitors sub-cycle is not feasible due to concerns of stored charge, a TCR is used to create a variable inductance to offset the capacitor. A TCSC can be used to dynamically vary the power flow on a transmission line.[16]

A VSC can also be used as a series compensation device if it's connected across the secondary winding of a series-connected transformer. This arrangement is referred to as a Static Synchronous Series Compensator (SSSC)[17], and offers the benefits of a smaller reactor than in a TCSC, and the lower harmonic production of a VSC (or Voltage-Source Inverter - VSI when used in a SSSC) compared to a TCR.

Phase Angle Compensation

Power will only flow between two points on an AC system if there is a phase angle difference between the buses. Traditionally this is controlled by generators, however in large grids this becomes ineffective for managing power flow between distant buses. Phase-Shifting Transformers (PST) are generally used for these applications and can just be a Phase-Angle Regulator (PAR) or control both phase-angle and voltage.

The most straightforward phase angle compensation device would be to replace the tap changer on PAR with thyristors to switch portions of the winding in and out, forming a Thyristor-Controlled Phase-Angle Regulator (TCPAR).[18] However, this is generally not done as a TCPAR would be considerably more expensive than a PAR. Instead, the idea of a TCPAR is expanded to replace a Quadrature Booster PST with a device referred to as a Static Phase Shifter (SPS).[19] From the schematic, it can be seen that a SPS is similar to a combining a TCVR and TCPAR, by replacing the mechanical portions of the excitor and booster transformers. respectively.

Another way to control a transformer with thyristor is through a Thyristor Controlled Voltage Regulator (TCVR)[20], which uses pairs of thyristors to switch parts of the secondary transformer's winding sub-cycle, effectively changing the secondary voltage produced dynamically. This arrangement forms a device very similar to Tap-Changer, and functions much like a TCR. Technically, while a TCVR just controls voltage and not phase angle, it could be used to replace the taps or a PAR, and a version of it is used is a SPS. It is also often lumped with phase angle compensation devices due to its similar topology.

See also

References

  1. ^ EPRI High Voltage Direct Current (HVDC) Transmission Reference Book EPRI, Palo Alto, CA: 2017. 1020401.
  2. ^ a b EPRI Increased Power Flow Guidebook—2017: Increasing Power Flow in Lines, Cables, and Substations. EPRI, Palo Alto, CA: 2017. 3002010150
  3. ^ Gujar, Abhilash (2020-11-06). "Reactive Power Compensation using Shunt Capacitors for Transmission Line Loaded Above Surge Impedance". 2020 IEEE International Conference for Innovation in Technology (INOCON). IEEE. pp. 1–4. doi:10.1109/INOCON50539.2020.9298284. ISBN 978-1-7281-9744-9. S2CID 230512769.
  4. ^ Kamel, Salah; Mohamed, Marwa; Selim, Ali; Nasrat, Loai S.; Jurado, Francisco (March 2019). "Power System Voltage Stability Based on Optimal Size and Location of Shunt Capacitor Using Analytical Technique". 2019 10th International Renewable Energy Congress (IREC). IEEE. pp. 1–5. doi:10.1109/IREC.2019.8754516. ISBN 978-1-7281-0140-8. S2CID 195831344.
  5. ^ Rissik, H., Mercury-Arc Current Converters, Pitman. 1941.
  6. ^ "1954: Morris Tanenbaum fabricates the first silicon transistor at Bell Labs". The Silicon Engine. Computer History Museum. Retrieved 23 August 2019.
  7. ^ Owen, Edward L. (August 2007). "Fiftieth anniversary of modern power electronics: The Silicon Controlled Rectifier". 2007 IEEE Conference on the History of Electric Power. pp. 201–211. doi:10.1109/HEP.2007.4510267. ISBN 978-1-4244-1343-0. S2CID 12720980.
  8. ^ Choudhary, Sunita; Mahela, Om Prakash; Ola, Sheesh Ram (November 2016). "Detection of transmission line faults in the presence of thyristor controlled reactor using discrete wavelet transform". 2016 IEEE 7th Power India International Conference (PIICON). IEEE. pp. 1–5. doi:10.1109/POWERI.2016.8077268. ISBN 978-1-4673-8962-4. S2CID 23488189.
  9. ^ Iwamuro, Noriyuki; Laska, Thomas (March 2017). "IGBT History, State-of-the-Art, and Future Prospects". IEEE Transactions on Electron Devices. 64 (3): 741–752. Bibcode:2017ITED...64..741I. doi:10.1109/TED.2017.2654599. ISSN 0018-9383. S2CID 36435533.
  10. ^ Kumar, Yogesh; Devabhaktuni, Vijay K.; Vemuru, Srinivasa (May 2015). "Comparison of power system simulation tools with load flow study cases". 2015 IEEE International Conference on Electro/Information Technology (EIT). IEEE. pp. 290–294. doi:10.1109/EIT.2015.7293355. ISBN 978-1-4799-8802-0.
  11. ^ Mohan, Ned (2007). First course on power systems (Year 2006 Edition; revised July 2007 ed.). Minneapolis: MNPERE. ISBN 978-0-9715292-7-4.
  12. ^ Hingorani, Narain G.; Gyugyi, Laszlo (2000). Understanding FACTS: concepts and technology of flexible AC transmission systems. New York: IEEE Press. ISBN 978-0-7803-3455-7.
  13. ^ EPRI Increased Power Flow Guidebook—2017: Increasing Power Flow in Lines, Cables, and Substations. EPRI, Palo Alto, CA: 2017. 3002010150.
  14. ^ EPRI Power Electronics-Based Transmission Controllers Reference Book ("The Gold Book") EPRI, Palo Alto, CA: 2017. 1020401.
  15. ^ Sood, Vijay K. (2004). HVDC and FACTS controllers: applications of static converters in power systems. Power electronics and power systems. Boston: Kluwer Academic Publishers. ISBN 978-1-4020-7890-3.
  16. ^ Cao, Foqing; Hu, Lei; Zhang, Jingtao; Almenweer, Reem A.; Alnasseir, Jamal; Almaghout, Fadi (2023-12-15). "Study on Power Flow Improvement Using Static Compensators and Thyristor Controlled Series Capacitor in Transmission Network". IEEE: 354–359. doi:10.1109/CEECT59667.2023.10420634. ISBN 979-8-3503-4225-3. {{cite journal}}: Cite journal requires |journal= (help)
  17. ^ Hingorani, Narain G.; Gyugyi, Laszlo (2000). Understanding FACTS: concepts and technology of flexible AC transmission systems. New York: IEEE Press. ISBN 978-0-7803-3455-7.
  18. ^ Rezvanfar, R.; Mosayebian, M. E.; Monsef, H.; Ghasemi, H. (2011-05). "Impact of optimally located thyristor controlled phase angle regulator on system security and reliability". 2011 10th International Conference on Environment and Electrical Engineering. IEEE. doi:10.1109/eeeic.2011.5874829. {{cite journal}}: Check date values in: |date= (help)
  19. ^ Song, Yong-hua; Johns, Allan T., eds. (1999). Flexible ac transmission systems (FACTS). IEE power and energy series. London: Institution of Electrical Engineers. ISBN 978-0-85296-771-3.
  20. ^ Asabin, Anatolij; Sosnina, Elena; Belyanin, Igor; Bedretdinov, Rustam; Kryukov, Evgeny (2020-06-29). "Control System of the Thyristor Voltage Regulator". IEEE: 802–806. doi:10.1109/CoDIT49905.2020.9263984. ISBN 978-1-7281-5953-9. {{cite journal}}: Cite journal requires |journal= (help)