Air source heat pump: Difference between revisions
Danielmwhite (talk | contribs) |
Danielmwhite (talk | contribs) |
||
Line 54: | Line 54: | ||
*Usually marketed as low energy or a sustainable technology, the HFCs have the potential to contribute to global warming{{Citation needed|date=September 2009}}. The effect the refrigerant could have is measured in [[global warming potential]] (GWP) and [[ozone depletion potential]] (ODP). |
*Usually marketed as low energy or a sustainable technology, the HFCs have the potential to contribute to global warming{{Citation needed|date=September 2009}}. The effect the refrigerant could have is measured in [[global warming potential]] (GWP) and [[ozone depletion potential]] (ODP). |
||
*Air source heat pumps lose their efficiency as external temperatures fall below 5 degrees celsius. In colder climates the system needs to be installed with an auxiliary source of heat to providing heat at low temperatures or if the heat pump should require repair. |
*Air source heat pumps lose their efficiency as external temperatures fall below 5 degrees celsius. In colder climates the system needs to be installed with an auxiliary source of heat to providing heat at low temperatures or if the heat pump should require repair. |
||
*The outdoor section on some units may "frost up" when outdoor temperatures are between 0°C and 5°C and there is sufficient moisture in the air{{Citation needed|date=November 2010}} which causes restriction of air flow across the outdoor coil. These units employ a time/delay or demand defrost cycle where the system a) switches to "a/c" mode for up to 10 minutes to move heat from the home to the outdoor section to melt the ice and b) turns on the supplemental heater (resistance electric, gas, etc.) in the indoor section to temper the cold air being distributed. The defrost cycle reduces the efficiency of the heat pump significantly, although the newer (demand) systems are more intelligent and need to defrost less. As temperatures drop below freezing the tendency for frosting of the outdoor section decreases due to reduced humidity in the air. An air source heat pump switching out of defrost mode in normal operation emits a characteristic "whoosh" sound from the outdoor section.{{Citation needed|date=November 2010}} Some systems are designed to cope with the defrost requirements of damp climates, ensuring that defrost cycles do not reduce heating performance. <ref>Damp Climate Performance</ref> |
*The outdoor section on some units may "frost up" when outdoor temperatures are between 0°C and 5°C and there is sufficient moisture in the air{{Citation needed|date=November 2010}} which causes restriction of air flow across the outdoor coil. These units employ a time/delay or demand defrost cycle where the system a) switches to "a/c" mode for up to 10 minutes to move heat from the home to the outdoor section to melt the ice and b) turns on the supplemental heater (resistance electric, gas, etc.) in the indoor section to temper the cold air being distributed. The defrost cycle reduces the efficiency of the heat pump significantly, although the newer (demand) systems are more intelligent and need to defrost less. As temperatures drop below freezing the tendency for frosting of the outdoor section decreases due to reduced humidity in the air. An air source heat pump switching out of defrost mode in normal operation emits a characteristic "whoosh" sound from the outdoor section.{{Citation needed|date=November 2010}} Some systems are designed to cope with the defrost requirements of damp climates, ensuring that defrost cycles do not reduce heating performance. <ref>[http://www.globalenergysystems.co.uk/features_products/why_eco_air_boilers.html Damp Climate Performance]</ref> |
||
*The COP is reduced when heat pumps are used to reach over 60°C for heating domestic water or in conventional [[central heating]] systems using radiators to distribute heat (instead of an underfloor heating array). |
*The COP is reduced when heat pumps are used to reach over 60°C for heating domestic water or in conventional [[central heating]] systems using radiators to distribute heat (instead of an underfloor heating array). |
||
*Retrofit is difficult when used with conventional heating systems using radiators or radiant panels. The lower Heat Pump output temperatures would mean radiators would have to be increased in size or a low temperature [[underfloor heating]] system be installed instead. |
*Retrofit is difficult when used with conventional heating systems using radiators or radiant panels. The lower Heat Pump output temperatures would mean radiators would have to be increased in size or a low temperature [[underfloor heating]] system be installed instead. |
Revision as of 13:04, 26 January 2011
This article is written like a personal reflection, personal essay, or argumentative essay that states a Wikipedia editor's personal feelings or presents an original argument about a topic. (August 2010) |
This article is written like a debate.(January 2011) |
An air source heat pump uses outside air as a heat source or heat sink. A compressor, condenser and refrigerant system is used to absorb heat at one place and release it at another.
General
Outside air, necessarily existing at some temperature above absolute zero, is a heat container. An air-source heat pump moves ("pumps") some of this heat to provide hot water or household heating. This can be done in either direction, to cool or heat the interior of a building.
The main components of an air-source heat pump are:
- a heat exchanger, over which outside air is blown, to extract the heat from the air
- a compressor, which acts like a refrigerator but in reverse and raises the temperature from the outside air
- a way to transfer the heat into a hot water tank or heating system, such as radiators or under-floor heating tubes
How air source heat pumps work
Heating and cooling is accomplished by moving a refrigerant through the heat pump's various indoor and outdoor coils and components. A compressor, condenser, expansion valve and evaporator are used to change states of the refrigerant from a liquid to hot gas and from a gas to a cold liquid. The refrigerant is used to heat or cool coils in a building or room and fans pull the room air over the coils. An external outdoor heat exchanger is used to heat or cool the refrigerant. This use of outside air has led to the term "Air Source" Heat Pump. The overall operation uses the concepts described in classic vapor compression refrigeration.
When the liquid refrigerant at a low temperature passes through the outdoor evaporator coils, the temperature of the outside air causes the liquid to boil. This change of state from liquid to a vapor requires a considerable amount of energy or "latent heat" which is provided by outside air passing over the coils.
This vapor is then drawn into the compressor where the temperature of the vapor is boosted to well over 100 degrees Celsius. At this point we have used heat from the outside air to change the liquid refrigerant to a gas and added an amount of compression "work" to raise the temperature of the vapor. The vapor now enters the condenser heat exchanger coils where it begins to transfer heat to the air being drawn across the coils. As the vapor cools, it condenses back to a liquid and in so doing releases and transfers considerable latent heat to the air passing over the condenser unit coils. We have used the heat energy of outside air to change the phase of the refrigerant and then released this heat for heating, a typical heat pump operation.
At this stage we now have a very cold liquid refrigerant compressed to a high pressure. The refrigerant is next passed through an expansion valve which turns it back to a low pressure cold liquid ready to re-enter the evaporator to begin a new cycle.
The heat pump can also operate in a cooling mode where the cold refrigerant is moved through the indoor coils to cool the room air.
Efficiency
The 'Efficiency' of air source heat pumps is measured by the Coefficient of performance (COP). In simple terms, a COP of 3 means the heat pump produces 3 units of heat energy for every 1 unit of electricity it consumes. In mild weather, the COP of an air source heat pump can be up to 4. However, on a very cold winter day, it takes more work to move the same amount of heat indoors than on a mild day. The heat pump's performance is limited by the Carnot cycle and will approach 1.0 as the outdoor-to-indoor temperature difference increases at around −18 °C (0 °F) outdoor temperature for air source heat pumps. However, heat pump construction methods that enable use of carbon dioxide refrigerant extend the figure downward to -30 °C (-22 °F). A Geothermal heat pump will have less change in COP as the ground temperature from which they extract heat is more constant than outdoor air temperature.
Seasonally adjusted heating and cooling efficiencies are given by the heating seasonal performance factor (HSPF) and seasonal energy efficiency ratio (SEER) respectively.
The efficiency of a heat pump can be significantly affected by its original design. Many air source heat pumps began life as air conditioning units, designed for summer temperatures. In designing a heat pump as a heat pump from inception great COPs and life cycles can be attained. The principal changes are in the scale and type of compressor and evaporator to allow COP of greater than 2 even down to -20°C.
Advantages and disadvantages
Advantages
- Typically draws approximately 1/3 to 1/4 of the electricity of a standard resistance heater for the same amount of heating, reducing utility bills.[1] This typical efficiency compares to 70-95% for a fossil fuel-powered boiler[citation needed].
- Few moving parts, reducing maintenance requirements. However, it should be ensured that the outdoor heat exchanger and fan is kept free from leaves and debris. Moreover, it must be borne in mind that a heat pump will have significantly more moving parts than an equivalent electric resistance heater or fuel burning heater.
- As an electric system, no flammable or potentially asphyxiating fuel is used at the point of heating, reducing the potential danger to users, and removing the need to obtain gas or fuel supplies (except for electricity).
- May be used to heat air, or water.
- The same system may be used for air conditioning in summer, as well as a heating system in winter.
- lower running costs, the compressor being the thing that uses most power - when in comparison with traditional electrical resistance heaters.[citation needed].
Disadvantages
The following disadvantages are associated with all air source heat pump designs:
- Air source heat pumps require electricity for operation. Electricity generation accounts for a significant amount of emissions pollutants and greenhouse gases.
- External space needs to be found for the outside condenser unit which can be somewhat noisy(comparable to an air conditioner unit) [citation needed] and possibly unsightly.
- The cost of installation is high (though less than a Ground Source heat pump because a ground source heat pump requires installation of a ground loop).
The following disadvantages are associated with units charged with HFC refrigerants:
- Usually marketed as low energy or a sustainable technology, the HFCs have the potential to contribute to global warming[citation needed]. The effect the refrigerant could have is measured in global warming potential (GWP) and ozone depletion potential (ODP).
- Air source heat pumps lose their efficiency as external temperatures fall below 5 degrees celsius. In colder climates the system needs to be installed with an auxiliary source of heat to providing heat at low temperatures or if the heat pump should require repair.
- The outdoor section on some units may "frost up" when outdoor temperatures are between 0°C and 5°C and there is sufficient moisture in the air[citation needed] which causes restriction of air flow across the outdoor coil. These units employ a time/delay or demand defrost cycle where the system a) switches to "a/c" mode for up to 10 minutes to move heat from the home to the outdoor section to melt the ice and b) turns on the supplemental heater (resistance electric, gas, etc.) in the indoor section to temper the cold air being distributed. The defrost cycle reduces the efficiency of the heat pump significantly, although the newer (demand) systems are more intelligent and need to defrost less. As temperatures drop below freezing the tendency for frosting of the outdoor section decreases due to reduced humidity in the air. An air source heat pump switching out of defrost mode in normal operation emits a characteristic "whoosh" sound from the outdoor section.[citation needed] Some systems are designed to cope with the defrost requirements of damp climates, ensuring that defrost cycles do not reduce heating performance. [2]
- The COP is reduced when heat pumps are used to reach over 60°C for heating domestic water or in conventional central heating systems using radiators to distribute heat (instead of an underfloor heating array).
- Retrofit is difficult when used with conventional heating systems using radiators or radiant panels. The lower Heat Pump output temperatures would mean radiators would have to be increased in size or a low temperature underfloor heating system be installed instead.
Conclusions
Air source heat pumps can provide fairly low cost space heating. A high efficiency heat pump can provide four times the heat compared to an electric heater.[3].
Air source heat pumps are sometimes used to provide hot water from a pressurized system up to temperatures of 55°C. To minimize the risk from Legionellosis it is advised that hot water is heated to above 60°C.
The overall lifetime costs for using air source heat pumps should be considered carefully as mains gas (where available) may be cheaper than electricity (although it has higher carbon emissions).
Air source heat pumps should last for over 20 years with low maintenance requirements.[4][5]