Bang–bang control
In control theory, a bang–bang controller (hysteresis, 2 step or on–off controller), is a feedback controller that switches abruptly between two states. These controllers may be realized in terms of any element that provides hysteresis. They are often used to control a plant that accepts a binary input, for example a furnace that is either completely on or completely off. Most common residential thermostats are bang–bang controllers. The Heaviside step function in its discrete form is an example of a bang–bang control signal. Due to the discontinuous control signal, systems that include bang–bang controllers are variable structure systems, and bang–bang controllers are thus variable structure controllers.
Bang–bang solutions in optimal control
In optimal control problems, it is sometimes the case that a control is restricted to be between a lower and an upper bound. If the optimal control switches from one extreme to the other (i.e., is strictly never in between the bounds), then that control is referred to as a bang–bang solution.
Bang–bang controls frequently arise in minimum-time problems. For example, if it is desired for a car starting at rest to arrive at a certain position ahead of the car in the shortest possible time, the solution is to apply maximum acceleration until the unique switching point, and then apply maximum braking to come to rest exactly at the desired position.
A familiar everyday example is bringing water to a boil in the shortest time, which is achieved by applying full heat, then turning it off when the water reaches a boil. A closed-loop household example is most thermostats, wherein the heating element or air conditioning compressor is either running or not, depending upon whether the measured temperature is above or below the setpoint.
Bang–bang solutions also arise when the Hamiltonian is linear in the control variable; application of Pontryagin's minimum or maximum principle will then lead to pushing the control to its upper or lower bound depending on the sign of the coefficient of u in the Hamiltonian.[1]
In summary, bang–bang controls are actually optimal controls in some cases, although they are also often implemented because of simplicity or convenience.
Practical implications of bang–bang control
Mathematically or within a computing context there may be no problems, but the physical realization of bang–bang control systems gives rise to several complications.
First, depending on the width of the hysteresis gap and inertia in the process, there will be an oscillating error signal around the desired set point value (e.g., temperature), often saw-tooth shaped. Room temperature may become uncomfortable just before the next switch 'ON' event. Alternatively, a narrow hysteresis gap will lead to frequent on/off switching, which is often undesirable (e.g. an electrically ignited gas heater).
Second, the onset of the step function may entail, for example, a high electrical current and/or sudden heating and expansion of metal vessels, ultimately leading to metal fatigue or other wear-and-tear effects. Where possible, continuous control, such as in PID control will avoid problems caused by the brisk state transitions that are the consequence of bang–bang control.
Pulse-width modulation
A PID controller can send pulse-width modulation control signals that reduce switching of motors, solenoids, etc. by setting "minimum ON times" and "minimum OFF times".[2]
See also
References
- ^ Kamien, Morton I.; Schwartz, Nancy L. (1991). "Discontinuous and Bang-Bang Control". Dynamic Optimization : The Calculus of Variances and Optimal Control in Economics and Management (Second ed.). Amsterdam: North-Holland. pp. 202–208. ISBN 0-444-01609-0. Archived from the original on 2022-01-25. Retrieved 2022-01-25.
- ^ [1] Honeywell User manual | Excel 15 W7760C Plant Controller System Engineering Guide.
Further reading
- Artstein, Zvi (1980). "Discrete and continuous bang-bang and facial spaces, or: Look for the extreme points". SIAM Review. 22 (2): 172–185. doi:10.1137/1022026. JSTOR 2029960. MR 0564562.
- Flugge-Lotz, Irmgard (1953). Discontinuous Automatic Control. Princeton University Press. ISBN 9780691653259.
- Hermes, Henry; LaSalle, Joseph P. (1969). Functional analysis and time optimal control. Mathematics in Science and Engineering. Vol. 56. New York—London: Academic Press. pp. viii+136. MR 0420366.
- Kluvánek, Igor; Knowles, Greg (1976). Vector measures and control systems. North-Holland Mathematics Studies. Vol. 20. New York: North-Holland Publishing Co. pp. ix+180. MR 0499068.
- Rolewicz, Stefan (1987). Functional analysis and control theory: Linear systems. Mathematics and its Applications (East European Series). Vol. 29 (Translated from the Polish by Ewa Bednarczuk ed.). Dordrecht; Warsaw: D. Reidel Publishing Co.; PWN—Polish Scientific Publishers. pp. xvi+524. ISBN 90-277-2186-6. MR 0920371. OCLC 13064804.
- Sonneborn, L.; Van Vleck, F. (1965). "The Bang-Bang Principle for Linear Control Systems". SIAM J. Control. 2: 151–159.