Insulation monitoring device

From Wikipedia, the free encyclopedia

This is an old revision of this page, as edited by Scotia70 (talk | contribs) at 13:25, 24 November 2015 (Link in Further Reading is broken (*[http://www.bender-ca.com/fileadmin/products/b/e/A-ISOMETER-ShipsOffshore_PROSP_en.pdf Electrical Safety on Ships, Offshore and Onshore])). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

An insulation monitoring device monitors the ungrounded system between an active phase conductor and earth. It is intended to give an alert (light and sound) or disconnect the power supply when the resistance between the two conductors drops below a set value, usually 50 kΩ (sample of IEC standard for medical applications). The main advantage is that the ungrounded or floating system allows a continuous operation of important consumers such as medical, chemical, military, etc.

Some manufacturers of monitors for these systems are capable of handling VFDs (Variable Frequency (Speed) Drives). Most, however are not due to issues with the DC-portions of the VFDs.

Most monitors work by injecting low level dc on the line and detecting. Some manufacturers use a patented AMP-monitoring principle (Adapted Measuring Pulse)[citation needed]