This is an old revision of this page, as edited by ClueBot NG (talk | contribs) at 11:37, 8 April 2014 (Reverting possible vandalism by 149.254.180.151 to older version. False positive? Report it. Thanks, ClueBot NG. (1784524) (Bot)). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

King's Cross fire
King's Cross fire, billowing smoke, station lights and fire engines.
A Police Car, three Fire Engines and an Ambulance outside King's Cross
Map
Details
Date18 November 1987
19:30
LocationKing's Cross underground station
CountryEngland
Statistics
Deaths31
Injured100
List of UK rail accidents by year

The King's Cross fire broke out on 18 November 1987 at approximately 19:30 at King's Cross St. Pancras tube station, a major interchange on the London Underground. The fire killed 31 people. As well as the mainline railway stations above ground and subsurface platforms for the Metropolitan lines,[note 1] there were platforms deeper underground for the Northern, Piccadilly, and Victoria lines. The fire started on an escalator serving the Piccadilly Line and approximately 15 minutes after being reported, as the first members of the London Fire Brigade were investigating, the fire flashed over, filling the underground ticket office with heat and smoke.

The subsequent public inquiry determined that the fire had started due to a lit match being dropped onto the escalator and suddenly increased in intensity due to a previously unknown trench effect. London Underground were strongly criticised for their attitude toward fires. Complacent because there had never been a fatal fire on the Underground, staff had been given little or no training to deal with fires or evacuation.

The publication of the report led to resignations of senior management in both London Underground and London Regional Transport and to the introduction of new fire safety regulations.

Fire

At King's Cross, as well as the mainline railway station above ground and subsurface platforms for the Metropolitan line, there are platforms deeper underground for the Northern, Piccadilly, and Victoria lines. There were two separate escalator shafts leading down to the Victoria and Piccadilly lines; the Northern line was reached from the Piccadilly line. Stairs connected the Piccadilly and Victoria line platforms[1] and from these there was a subway to platforms used by British Rail Midland City (later Thameslink) trains to Moorgate and an entrance in Pentonville Road.[2]

At about 19:30 several passengers reported seeing a fire on a Piccadilly line escalator. Staff and police went to investigate and on confirming the fire one of the policemen went to the surface to radio for the fire brigade.[3] Four fire appliances and a turntable ladder were dispatched at 19:36 by the London Fire Brigade.[4] The fire was beneath the escalator, impossible to get close enough to use a fire extinguisher. There was water fog equipment but staff had not been trained in its use.[5] The decision to evacuate the station was made at 19:39, using the Victoria line escalators.[6] A few minutes later the fire brigade arrived and several firemen went down to the escalator to assess the fire. They saw a fire about the size of a large cardboard box and plans were made to fight it with a water jet using men with breathing apparatus.[7]

At 19:45 flashover occurred and a jet of flames came from the escalator shaft filling the ticket hall with intense heat and thick black smoke, [8] killing or seriously injuring most of the people in the ticket hall.[9] This trapped several hundred people below ground, who escaped on Victoria line trains.[10] A number of policemen with an injured man attempted to leave via the Midland City platforms, but found their way blocked by locked gates until these were unlocked by a cleaner.[11] Staff and a policewoman trapped on a Metropolitan line platform were rescued by a train.[10]

Thirty fire crews—over 150 firefighters—were deployed.[12] Fourteen London Ambulance Service ambulances ferried the injured to local hospitals, including University College Hospital.[13] The fire was declared out at 01:46 the following morning.[14]

Thirty-one people died[15] and 100 people were taken to hospital, 19 with serious injuries.[16] Fire Brigade station officer Colin Townsley was in charge of the first pump fire engine to arrive at the scene and was down in the ticket hall at the time of the flashover. He did not survive, his body being found beside that of a badly burnt passenger at the base of the exit steps to Pancras Road. It is believed that Townsley spotted the passenger in difficulty and stopped to help her.[17]

An initially unidentified man, commonly known as "Michael" or "Body 115" after its mortuary tag, was eventually identified on 22 January 2004, when forensic evidence confirmed he was 73-year-old Alexander Fallon of Falkirk, Scotland.[18] He was the subject of a 1990 Nick Lowe song, "Who Was That Man?"[citation needed]

Aftermath

The ticket hall and platforms for the Metropolitan line were undamaged and reopened the morning after the fire; the Victoria line, its escalators only slightly damaged, resumed normal operation on the following Tuesday. The ticket hall for the three tube lines was reopened in stages over a period of four weeks.[16] The three escalators for the Piccadilly line had to be completely replaced, the new ones being commissioned on 27 February 1989, more than 16 months after the fire. Until that time, the only access to the Piccadilly line was via the Victoria line or Midland City platforms, and at peak hours was possible in one direction only.[19]

Access to the Northern line platforms was indirect, its escalators connecting with the Piccadilly line. As the traffic from all three tube lines would have overcrowded the Victoria line escalators, Northern line trains ran through without stopping until repairs were complete. The nearly life-expired Northern line escalators were replaced as well and the Northern line station reopened, completing the return to normal operation, on 5 March 1989.[20]

Investigation and report

A public inquiry into the incident was conducted by Desmond Fennell, OBE QC, assisted by a panel of four expert advisers. The inquiry opened at Central Hall, Westminster on 1 February 1988 and closed on 24 June, after hearing 91 days of evidence.[21]

Wooden escalators at Greenford tube station in 2006, similar to those that caught fire at King's Cross. The escalator was eventually decommissioned on 10 March 2014 so as to make the station to have step-free access.

Although smoking had been banned on underground sections of the London Underground in February 1985 (a consequence of the Oxford Circus fire), the inquiry found the fire was most probably caused by a traveller discarding a burning match that fell down the side of the moving staircase on to the running track of the escalator.[22] The possibility that the fire had been started deliberately was discounted by police, as there was no evidence that an accelerant had been used and access to the site of the fire was difficult. Investigators found charred wood in eight places on a section of skirting on an escalator and matches in the running track,[23] showing that similar fires had started before but had burnt themselves out without spreading.[24] These combustion points were on the right-hand side, where standing passengers are most likely to light a cigarette (passengers stand on the right to let walking passengers pass on the left).[citation needed] Smoking on Underground trains was banned in July 1984 and following a fire at Oxford Circus station the ban was extended to all underground stations but smokers often ignored this and lit cigarettes on the escalators on their way out.[25] The investigators found a build-up of grease under the tracks, which was believed to be difficult to ignite and slow to burn once it started, but it was noted that the grease was heavily impregnated with fibrous materials. A test was conducted where lit matches were dropped on the escalator to see if ignition would occur. Matches dropped did ignite the contaminated grease and the fire began spreading, being allowed to burn for nine minutes before being extinguished.[26]

This test replicated the initial eyewitness reports up to that point but four expert witnesses could not agree as to how the small fire flashed over, with some concern that the paint used on the ceiling had contributed to the fire.[27] A model of King's Cross station was built at the Atomic Energy Research Establishment using computer simulation software; this showed the flames first spreading along the floor of the escalator, rather than burning vertically and suddenly producing a jet of flame into the ticket hall, matching the tube fire.[28] A fire behaved as in the computer model during experiments with a third scale replica of the escalator.[29] The metal sides of the escalator contained the flames and directed hot air ahead of the fire.[30] Sensors indicated that wooden treads for 20 feet in front of the flames (corresponding to 60 feet of track in the actual-size disaster) quickly reached between 500°C and 600°C. When the treads of the escalator flashed over, the size of the fire increased exponentially and a sustained jet of flame was discharged from the escalator tunnel into the model ticket hall.[citation needed] The conclusion was that this newly discovered trench effect had caused the fire to flashover at 19:45.[31]

London Underground were strongly criticised in the report for their attitude to fires underground, underestimating the hazard because no one had died in a fire.[32] Staff were expected to send for the Fire Brigade only if the fire was out of control, dealing with it themselves if possible.[33] Fires were called smouldering and staff had little or no training to deal with fires or evacuation.[32]

Legacy

Memorial plaque to the 1987 fire in the station

The publication of the report led to resignations of senior management of both London Underground and London Regional Transport. Wooden panelling was to be removed from escalators, heat detectors and sprinklers were to be fitted beneath escalators, and the radio communication system and station staff emergency training were to be improved.[34][35]

The Fire Precautions (Sub-surface Railway Stations) Regulations 1989 were introduced. Smoking was banned in all London Underground stations, including on the escalators, on 23 November, five days after the fire. Wooden escalators were gradually replaced, some remaining into the early 2000s (Wanstead replacing theirs in 2003 and Marylebone in 2004[36]) and as of 2014 the entire London Underground was operating on metal escalators, after the last wooden escalator at Greenford tube station was decommissioned on 10 March 2014.

Six firemen received Certificates of Commendation for their actions at the fire, including Station Officer Townsley who was given the award posthumously.[37] Station Officer Townsley was also posthumously awarded the George Medal.[38]

Soon after the fire a commemoration service was held at St Pancras Church.[39] Further commemoration services were held on 18 November 1997, the tenth anniversary of the blaze,[citation needed] on the twentieth anniversary in 2007 at the station itself[39] and on the twenty-fifth anniversary in 2012 at the Church of the Blessed Sacrament near the station.[40]

Memorial plaques commemorating the disaster were installed at St Pancras Church, unveiled by the Princess of Wales, and at King's Cross station.[39]

Notes and references

Notes

  1. ^ Circle line trains also call at these platforms.

References

  1. ^ Fennell 1988, figure 6.
  2. ^ Fennell 1988, figure 5.
  3. ^ Fennell 1988, p. 49.
  4. ^ Fennell 1988, p. 50.
  5. ^ Fennell 1988, pp. 51, 62.
  6. ^ Fennell 1988, p. 51.
  7. ^ Fennell 1988, p. 52.
  8. ^ Fennell 1988, p. 53.
  9. ^ Fennell 1988, p. 100.
  10. ^ a b Fennell 1988, p. 54.
  11. ^ Fennell 1988, pp. 54, 56.
  12. ^ Fennell 1988, p. 82.
  13. ^ Fennell 1988, p. 91.
  14. ^ Fennell 1988, p. 57.
  15. ^ Fennell 1988, p. 17.
  16. ^ a b Croome & Jackson 1993, p. 459.
  17. ^ Fennell 1988, pp. 78–79.
  18. ^ Jonathan Duffy (22 January 2004). "Solved after 16 years - the mystery of victim 115". BBC News Online. Retrieved 28 October 2012.
  19. ^ Croome & Jackson 1993, pp. 459, 462.
  20. ^ Croome & Jackson 1993, pp. 459–462.
  21. ^ Fennell 1988, pp. 21–23.
  22. ^ Fennell 1988, p. 111.
  23. ^ Fennell 1988, pp. 221–224.
  24. ^ Fennell 1988, p. 114.
  25. ^ Fennell 1988, p. 94.
  26. ^ Fennell 1988, p. 104.
  27. ^ Fennell 1988, pp. 105–106.
  28. ^ Fennell 1988, p. 107.
  29. ^ Fennell 1988, p. 110.
  30. ^ Fennell 1988, p. 113.
  31. ^ Fennell 1988, pp. 113–114.
  32. ^ a b Fennell 1988, pp. 17–18.
  33. ^ Fennell 1988, p. 61.
  34. ^ Paul Channon (12 April 1989). http://hansard.millbanksystems.com/commons/1989/apr/12/kings-cross-fire-fennell-report#S6CV0150P0_19890412_HOC_145. Parliamentary Debates (Hansard). House of Commons. col. 915–917. {{cite book}}: |chapter-url= missing title (help)
  35. ^ "Sir Desmond Fennell". The Daily Telegraph. 5 July 2011.
  36. ^ An End To Treading the Boards, Metronet Matters, Issue 3: Metronet, 2004, p. 17 {{citation}}: |access-date= requires |url= (help)CS1 maint: location (link)
  37. ^ "RMT calls for staffing cuts to be scrapped on 25th anniversary of Kings Cross fire". London Evening Standard. 18 November 2012.
  38. ^ "London Gazette, 25 May 1989 (supplement to Gazette of 24 May 1989), number 51745, 6217" (PDF).
  39. ^ a b c "Ceremony marks King's Cross fire". BBC News. 17 November 2007. Retrieved 20 April 2013.
  40. ^ "King's Cross fire 25th anniversary marked". bbc.co.uk. 19 November 2012. Retrieved 19 November 2012.

Sources

Further reading

  • Appleton, B. (1992). Report of an inquiry into health and safety aspects of stoppages caused by fire and bomb alerts on London Underground, British Rail and other mass transit systems. HSE Books. ISBN 0-11-886394-0.
  • Chambers, P. (2006). Body 115: The Story of the Last Victim of the King's Cross Fire. John Wiley & Sons. ISBN 0-470-01808-9.
  • Moodie, K. (1992). "The King's Cross Fire: Damage Assessment and Overview of the Technical Investigation". Fire Safety Journal, vol 18.
  • Simcox, S.; Wilkes, N.S.; Jones, I.P. (1992). "Computer Simulation of the Flows of Hot Gases from the Fire at King's Cross Underground Station". Fire Safety Journal, vol 18.
  • Vaughan, Adrian (2000). Tracks to Disaster. Ian Allan. ISBN 0-7110-2731-5. {{cite book}}: Cite has empty unknown parameter: |coauthors= (help)
  • Institution of Mechanical Engineers Environmental Engineering Group (1 June 1989). The King's Cross underground fire: fire dynamics and the organization of safety. Mechanical Engineering Publications. ISBN 978-0-85298-705-6.
  • White, Rose. WHOOSH! Kings Cross Fire Mystery Solved. ASIN B00BFVJK0O.
UK Legislation

51°31′50″N 0°07′26″W / 51.53048°N 0.12385°W / 51.53048; -0.12385