Nusselt number

From Wikipedia, the free encyclopedia

This is an old revision of this page, as edited by Millennium bug (talk | contribs) at 17:29, 12 October 2015 (Reverted edits by 104.178.115.26 (talk) (HG) (3.1.16)). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

In heat transfer at a boundary (surface) within a fluid, the Nusselt number (Nu) is the ratio of convective to conductive heat transfer across (normal to) the boundary. In this context, convection includes both advection and diffusion. Named after Wilhelm Nusselt, it is a dimensionless number. The conductive component is measured under the same conditions as the heat convection but with a (hypothetically) stagnant (or motionless) fluid. A similar non-dimensional parameter is Biot Number, with the difference that the thermal conductivity is of the solid body and not the fluid.

A Nusselt number close to one, namely convection and conduction of similar magnitude, is characteristic of "slug flow" or laminar flow. A larger Nusselt number corresponds to more active convection, with turbulent flow typically in the 100–1000 range.

The convection and conduction heat flows are parallel to each other and to the surface normal of the boundary surface, and are all perpendicular to the mean fluid flow in the simple case.

where h is the convective heat transfer coefficient of the flow, L is the characteristic length, k is the thermal conductivity of the fluid.

  • Selection of the characteristic length should be in the direction of growth (or thickness) of the boundary layer; some examples of characteristic length are: the outer diameter of a cylinder in (external) cross flow (perpendicular to the cylinder axis), the length of a vertical plate undergoing natural convection, or the diameter of a sphere. For complex shapes, the length may be defined as the volume of the fluid body divided by the surface area.
  • The thermal conductivity of the fluid is typically (but not always) evaluated at the film temperature, which for engineering purposes may be calculated as the mean-average of the bulk fluid temperature and wall surface temperature.

In contrast to the definition given above, known as average Nusselt number, local Nusselt number is defined by taking the length to be the distance from the surface boundary[1] to the local point of interest.

The mean, or average, number is obtained by integrating the expression over the range of interest, such as:[2]

The mass transfer analog of the Nusselt number is the Sherwood number.

Introduction

An understanding of convection boundary layers is necessary to understanding convective heat transfer between a surface and a fluid flowing past it. A thermal boundary layer develops if the fluid free stream temperature and the surface temperatures differ. A temperature profile exists due to the energy exchange resulting from this temperature difference.

Thermal Boundary Layer

The heat transfer rate can then be written as,

And because heat transfer at the surface is by conduction,

These two terms are equal; thus

Rearranging,

Making it dimensionless by multiplying by representative length L,

The right hand side is now the ratio of the temperature gradient at the surface to the reference temperature gradient. While the left hand side is similar to the Biot modulus. This becomes the ratio of conductive thermal resistance to the convective thermal resistance of the fluid, otherwise known as the Nusselt number, Nu.

Derivation

The Nusselt number may be obtained by a non dimensional analysis of Fourier's law since it is equal to the dimensionless temperature gradient at the surface:

, where q is the heat flux, k is the constant thermal conductivity and T the fluid temperature.

Indeed if: , and

we arrive at

then we define

so the equation becomes

By integrating over the surface of the body:

,

where

Empirical Correlations

Typically, for free convection, the average Nusselt number is expressed as a function of the Rayleigh number and the Prandtl number, written as:

Otherwise, for forced convection, the Nusselt number is generally a function of the Reynolds number and the Prandtl number, or

Empirical correlations for a wide variety of geometries are available that express the Nusselt number in the aforementioned forms.

Free convection

Free convection at a vertical wall

Cited[3] as coming from Churchill and Chu:

Free convection from horizontal plates

If the characteristic length is defined

where is the surface area of the plate and is its perimeter.

Then for the top surface of a hot object in a colder environment or bottom surface of a cold object in a hotter environment[3]

And for the bottom surface of a hot object in a colder environment or top surface of a cold object in a hotter environment[3]

Forced convection on flat plate

Flat plate in laminar flow

The local Nusselt number for laminar flow over a flat plate is given by[4]

Flat plate in laminar flow

The average Nusselt number for laminar flow over a flat plate is given by[4]

[5]

Forced convection in turbulent pipe flow

Gnielinski correlation

Gnielinski's correlation for turbulent flow in tubes:[4]

where f is the Darcy friction factor that can either be obtained from the Moody chart or for smooth tubes from correlation developed by Petukhov:[4]

The Gnielinski Correlation is valid for:[4]

Dittus-Boelter equation

The Dittus-Boelter equation (for turbulent flow) is an explicit function for calculating the Nusselt number. It is easy to solve but is less accurate when there is a large temperature difference across the fluid. It is tailored to smooth tubes, so use for rough tubes (most commercial applications) is cautioned. The Dittus-Boelter equation is:

where:

is the inside diameter of the circular duct
is the Prandtl number
for heating of the fluid, and for cooling of the fluid.[3]

The Dittus-Boelter equation is valid for [6]

Example The Dittus-Boelter equation is a good approximation where temperature differences between bulk fluid and heat transfer surface are minimal, avoiding equation complexity and iterative solving. Taking water with a bulk fluid average temperature of 20 °C, viscosity 10.07×10−4 Pa·s and a heat transfer surface temperature of 40 °C (viscosity 6.96×10−4, a viscosity correction factor for can be obtained as 1.45. This increases to 3.57 with a heat transfer surface temperature of 100 °C (viscosity 2.82×10−4 Pa·s), making a significant difference to the Nusselt number and the heat transfer coefficient.

Sieder-Tate correlation

The Sieder-Tate correlation for turbulent flow is an implicit function, as it analyzes the system as a nonlinear boundary value problem. The Sieder-Tate result can be more accurate as it takes into account the change in viscosity ( and ) due to temperature change between the bulk fluid average temperature and the heat transfer surface temperature, respectively. The Sieder-Tate correlation is normally solved by an iterative process, as the viscosity factor will change as the Nusselt number changes.[7]

[3]

where:

is the fluid viscosity at the bulk fluid temperature
is the fluid viscosity at the heat-transfer boundary surface temperature

The Sieder-Tate correlation is valid for[3]

Forced convection in fully developed laminar pipe flow

For fully developed internal laminar flow, the Nusselt numbers are constant-valued. The values depend on the hydraulic diameter.

For internal Flow:

where:

Dh = Hydraulic diameter
kf = thermal conductivity of the fluid
h = convective heat transfer coefficient

Convection with uniform surface heat flux for circular tubes

From Incropera & DeWitt,[8]

Convection with uniform surface temperature for circular tubes

For the case of constant surface temperature,[8]

See also

References

  1. ^ Yunus A. Çengel (2003). Heat Transfer: a Practical Approach (2nd ed.). McGraw-Hill.
  2. ^ E. Sanvicente; et al. (2012). "Transitional natural convection flow and heat transfer in an open channel". International Journal of Thermal Sciences. 63: 87–104. doi:10.1016/j.ijthermalsci.2012.07.004.
  3. ^ a b c d e f Incropera, Frank P.; DeWitt, David P. (2000). Fundamentals of Heat and Mass Transfer (4th ed.). New York: Wiley. p. 493. ISBN 0-471-30460-3.
  4. ^ a b c d e Incropera, Frank P.; DeWitt, David P. (2007). Fundamentals of Heat and Mass Transfer (6th ed.). Hoboken: Wiley. pp. 490, 515. ISBN 978-0-471-45728-2.
  5. ^ Incropera, Frank P. Fundamentals of heat and mass transfer. John Wiley & Sons, 2011.
  6. ^ Incropera, Frank P.; DeWitt, David P. (2007). Fundamentals of Heat and Mass Transfer (6th ed.). New York: Wiley. p. 514. ISBN 978-0-471-45728-2.
  7. ^ "Temperature Profile in Steam Generator Tube Metal" (PDF). Retrieved 23 September 2009.
  8. ^ a b Incropera, Frank P.; DeWitt, David P. (2002). Fundamentals of Heat and Mass Transfer (5th ed.). Hoboken: Wiley. pp. 486, 487. ISBN 0-471-38650-2.