Jump to content

Variable refrigerant flow

From Wikipedia, the free encyclopedia

This is an old revision of this page, as edited by R'n'B (talk | contribs) at 20:50, 1 October 2023 (Disambiguating links to Energy efficiency (link changed to Efficient energy use) using DisamAssist.). The present address (URL) is a permanent link to this revision, which may differ significantly from the current revision.

Variable refrigerant flow (VRF), also known as variable refrigerant volume (VRV), is an HVAC technology invented by Daikin Industries, Ltd. in 1982.[1] Similar to ductless mini-split systems, VRFs use refrigerant as the primary cooling and heating medium, and is usually less complex than conventional chiller-based systems. This refrigerant is conditioned by one or more condensing units (which may be outdoors or indoors, water or air cooled), and is circulated within the building to multiple indoor units.[2] VRF systems, unlike conventional chiller-based systems, allow for varying degrees of cooling in more specific areas (because there are no large air handlers, only smaller indoor units), may supply hot water in a heat recovery configuration without affecting efficiency,[3] and switch to heating mode (heat pump) during winter without additional equipment, all of which may allow for reduced energy consumption. Also, air handlers and large ducts are not used which can reduce the height above a dropped ceiling as well as structural impact as VRF uses smaller penetrations for refrigerant pipes instead of ducts.[4]

Description

VRFs are typically installed with an air conditioner inverter which adds a DC inverter to the compressor in order to support variable motor speed and thus variable refrigerant flow rather than simply perform on/off operation. By operating at varying speeds, VRF units work only at the needed rate allowing for substantial energy savings at load conditions. Heat recovery VRF technology allows individual indoor units to heat or cool as required, while the compressor load benefits from the internal heat recovery. Energy savings of up to 55% are predicted over comparable unitary equipment.[1] [5] This also results in greater control of the building's interior temperature by the building's occupants. The lower start-up power of VRF's DC inverter compressors and their inherent DC power requirements also allow VRF solar-powered heat pumps to be run using DC-providing solar panels.

VRFs come in two system formats, two pipe and three pipe systems. In a heat pump two pipe system all of the zones must either be all in cooling or all in heating. Heat Recovery (HR) systems have the ability to simultaneously heat certain zones while cooling others; this is usually done through a three pipe design, with the exception of Mitsubishi, Carrier and LG whose systems are able to do this with a two pipe system using a branch circuit (BC) controller to the individual indoor evaporator zones. In this case the heat extracted from zones requiring cooling is put to use in the zones requiring heating. This is made possible because the heating unit is functioning as a condenser, providing sub-cooled liquid back into the line that is being used for cooling. While the heat recovery system has a greater initial cost, it allows for better zoned thermal control of a building and overall greater efficiencies.[6] In heat recovery VRF systems, some of the indoor units may be in cooling mode while others are in heating mode, reducing energy consumption. If the coefficient of performance in cooling mode of a system is 3, and the coefficient of performance in heating mode is 4, then heat recovery performance can reach more than 7. While it is unlikely that this balance of cooling and heating demand will happen often throughout the year, energy efficiency can be greatly improved when the scenario occurs.[7]

VRF systems may be air or water cooled. If air cooled, VRF condensing units are exposed to outside air and may be outdoors, and condensing units are the size of large refrigerators, since they need to contain a large condenser (heat exchanger) which has a large surface area to transfer heat to the surrounding air, because air doesn't have a high heat capacity[8] and has a low density, volumetric thermal capacity and thermal conductivity thus needing to transfer heat into a large amount of air volume at once. If water cooled, the condensing units are placed indoors and are much smaller and cooled with water by a closed type or circuit cooling tower or dry cooler.

Japan

VRF systems have been used in Japan since the 1980s. By 2007, in Japan, VRFs are used in 50% of midsize office buildings (up to 70,000 ft2 or 6,500 m2) and 33% of large commercial buildings (more than 70,000 ft2 or 6,500 m2).[6] Daikin, a Japanese company, is the inventor of variable refrigerant volume systems (or VRV by Daikin air conditioning, other manufacturers remarketed this as VRF as VRV is a trademark).

Home automation integration

There are dedicated gateways that connect VRFs with home automation and building management systems (BMS) controllers for centralized control and monitoring. In addition, such gateway solutions are capable of providing remote control operation of all HVAC indoor units over the internet incorporating a simple and friendly user interface.[9][10]

Primary manufacturers

Japan:

Korea:

India:

Bangladesh:

Italy:

United States:

France:

China/Other:

References

  1. ^ a b Thornton, Brian (December 2012). Variable Refrigerant Flow Systems (PDF). General Services Administration (Report). US Federal Government. Archived from the original (PDF) on 2022-01-20. Retrieved 2013-08-06.
  2. ^ "VRF – "Reason to choose VRF HVAC Technology" – 22-7 Website". Retrieved 2019-09-05.
  3. ^ https://oaktrust.library.tamu.edu/bitstream/handle/1969.1/5243/ESL-IC-06-11-104.pdf?sequence=4&isAllowed=y [bare URL PDF]
  4. ^ Felt, Justin (2017-12-21). "The Emergence of VRF as a Viable HVAC Option". Buildings. Endeavor Business Media. Archived from the original on 2023-02-10.
  5. ^ "Variable Refrigerant Flow".
  6. ^ a b Goetzler (April 2007). "Variable Refrigerant Flow Systems". ASHRAE Journal: 24–31.
  7. ^ Rostamabadi, Mehrdad (2017). VRF HVAC Systems. Shafaf.
  8. ^ GF. Hundy, A.R. Trott, T.C. Welch, Chapter 6 - Condensers and Cooling Towers, Editor(s): G.F. Hundy, A.R. Trott, T.C. Welch, Refrigeration, Air Conditioning and Heat Pumps (Fifth Edition), Butterworth-Heinemann, 2016, Pages 99-120, ISBN 9780081006474, https://doi.org/10.1016/B978-0-08-100647-4.00006-1
  9. ^ "Cool Automation's CoolMasterNet Features IP Connectivity, Multi-Brand HVAC Support". CE Pro. Retrieved 16 November 2015.
  10. ^ "Air Condition Repair". Tuesday, 10 August 2021
  11. ^ "Toshiba Carrier Global | Air conditioner for residential, commercial and industrial uses". www.toshiba-carrier.co.jp.
  12. ^ "AHI Carrier Contacts". www.ahi-toshiba.com.
  13. ^ "Toshiba Carrier Ductless Heat Pump System - RAS-LAV/LKV | Carrier - Home Comfort". Carrier.
  14. ^ "Toshiba Carrier Variable Refrigerant Flow Systems | Carrier Commercial Systems North America". Carrier.
  15. ^ "VRF IFM Series". waltonbd.com. Retrieved 2023-07-19.
  16. ^ "VRF: Bosch Enters the Market". rac. 15 January 2016.
  17. ^ "Bosch enters VRF". Cooling Post. April 1, 2015.
  18. ^ "VRF systems | Products |". Buderus.

Further reading